- The%20XiFoam%20model%2Fsolver%20gave%20an%20overall%20acceptable%20model%20performance%20for%20both%20geometries%20and%20gas%20composition. obtainsSupportFrom j.jlp.2022.104761 assertion.
- The%20highest%20maximum%20pressure%20for%20the%20High%20LBV%20Li-ion%20gas%20was%20156%20kPa%20%28gauge%29%2C%20recorded%20at%20PS3%20in%20case%2010%20%28%CF%86%20%3D%201.38%29. obtainsSupportFrom j.jlp.2022.104761 assertion.
- In%20the%20numerical%20simulations%2C%20the%20highest%20maximum%20pressure%20of%2089%20kPa%20%28gauge%29%20was%20in%20the%20High%20CFD%201.2%20Inner%20case. obtainsSupportFrom j.jlp.2022.104761 assertion.
- For%20the%20Simplified%20Li-ion%20gas%20experiments%2C%20the%20highest%20maximum%20pressure%20peak%20was%2056%20kPa%20%28gauge%29%20%28at%20PS1%29%20in%20case%2026%20%28%CF%86%20%3D%201.10%29. obtainsSupportFrom j.jlp.2022.104761 assertion.
- The%20highest%20simulated%20maximum%20pressure%20was%2077%20kPa%20%28gauge%29%20%28at%20PS2%29%20in%20the%20Simple%20CFD%201.0%20Inner%20case%20for%20the%20Simplified%20Li-ion%20gas. obtainsSupportFrom j.jlp.2022.104761 assertion.
- For%20the%20High%20LBV%20Li-ion%20gas%20in%20the%20center%20channel%20geometry%2C%20the%20highest%20experimental%20maximum%20pressure%20of%20223%20kPa%20%28gauge%29%20was%20measured%20at%20PS3%20for%20case%2041%20%28%CF%86%20%3D%201.09%29. obtainsSupportFrom j.jlp.2022.104761 assertion.
- The%20highest%20simulated%20maximum%20pressure%20of%2094%20kPa%20%28gauge%29%20for%20High%20LBV%20Li-ion%20gas%20was%20measured%20at%20PS1%20for%20the%20High%20CFD%201.2%20Center%20case. obtainsSupportFrom j.jlp.2022.104761 assertion.
- The%20highest%20maximum%20pressure%20peaks%20for%20the%20Simplified%20Li-ion%20gas%20were%2055%20kPa%20%28gauge%29%20measured%20at%20PS1%20in%20case%2058%20%28%CF%86%20%3D%201.01%29. obtainsSupportFrom j.jlp.2022.104761 assertion.
- The%20highest%20simulated%20maximum%20pressure%20for%20Simplified%20Li-ion%20gas%20was%20119%20kPa%20%28gauge%29%20at%20PS1%20in%20simulation%20case%20Simple%20CFD%201.0%20Center. obtainsSupportFrom j.jlp.2022.104761 assertion.
- The%20maximum%20experimental%20positive%20impulse%20was%20188%20kPa%20ms%20and%20160%20kPa%20ms%20for%20the%20High%20LBV%20Li-ion%20gas%20%28case%2011%2C%20%CF%86%20%3D%201.47%29%20and%20the%20Simplified%20Li-ion%20gas%20%28case%2026%2C%20%CF%86%20%3D%201.10%29%20in%20the%20inner%20channel%20geometry%2C%20respectively. obtainsSupportFrom j.jlp.2022.104761 assertion.
- In%20the%20simulations%2C%20the%20maximum%20positive%20impulse%20was%20313%20kPa%20ms%20%28High%20CFD%201.2%20Inner%29%20and%20280%20kPa%20ms%20%28Simple%20CFD%201.0%20Inner%29%20for%20the%20High%20LBV%20Li-ion%20gas%20and%20the%20Simplified%20Li-ion%20gas%2C%20respectively. obtainsSupportFrom j.jlp.2022.104761 assertion.
- For%20the%20High%20LBV%20Li-ion%20gas%20in%20the%20center%20channel%20geometry%2C%20the%20experimental%20maximum%20positive%20impulse%20was%20591%20kPa%20ms%20%28case%2042%2C%20%CF%86%20%3D%201.18%29. obtainsSupportFrom j.jlp.2022.104761 assertion.
- In%20the%20simulation%2C%20the%20maximum%20positive%20impulse%20for%20High%20LBV%20Li-ion%20gas%20was%20666%20kPa%20ms%20for%20case%20High%20CFD%201.2%20Center. obtainsSupportFrom j.jlp.2022.104761 assertion.
- The%20highest%20maximum%20positive%20impulses%20for%20the%20Simplified%20Li-ion%20gas%20in%20experiments%20was%20324%20kPa%20ms%20%28case%2058%2C%20%CF%86%20%3D%201.01%29. obtainsSupportFrom j.jlp.2022.104761 assertion.
- In%20the%20simulation%2C%20the%20maximum%20positive%20impulse%20for%20Simplified%20Li-ion%20gas%20was%20743%20kPa%20ms%20measured%20in%20the%20Simple%20CFD%201.0%20Center%20case. obtainsSupportFrom j.jlp.2022.104761 assertion.
- The%20overall%20average%20MG%20and%20VG%20for%20the%20High%20LBV%20Li-ion%20gas%20in%20the%20inner%20channel%20geometry%20were%200.96%20and%201.26%2C%20respectively. obtainsSupportFrom j.jlp.2022.104761 assertion.
- The%20overall%20average%20MG%20and%20VG%20for%20the%20Simplified%20Li-ion%20gas%20in%20the%20inner%20channel%20geometry%20were%200.89%20and%201.36%2C%20respectively. obtainsSupportFrom j.jlp.2022.104761 assertion.
- The%20overall%20averaged%20MG%20and%20VG%20values%20were%201.10%20and%201.14%20for%20the%20High%20LBV%20Li-ion%20gas%20in%20the%20center%20channel%20geometry%2C%20respectively. obtainsSupportFrom j.jlp.2022.104761 assertion.
- For%20the%20Simplified%20Li-ion%20gas%2C%20the%20overall%20average%20MG%20and%20VG%20values%20were%200.80%20and%201.86%20in%20the%20center%20channel%20geometry%2C%20respectively. obtainsSupportFrom j.jlp.2022.104761 assertion.